1001 MAGNETIC FLOAT LEVEL TRANSMITTER – MAGNETOSTRICTIVE

Process connection:
Accuracy:
Guide tube length:
Specific gravity:
Design pressure:
Design temperature:
Material quality:
Stainless steel terminal box / Stainless steel terminal box with LED display
Threaded connection / Flange / Try-Clamp / Aseptic blind cone
0.2 mm
≤ 6000 mm
≥ 400 kg/m3
-1 bar … 40 bar
-40°C … 250°C
Stainless steel / Titanium / Polyamide / PVC / Polypropylene / PVDF /
Stainless steel E-CTFE coated / Stainless steel PFA coated
  Optional:    
Level switch function:
Temperature switch:
Temperature probe:

Description

The magnetic float level transmitter device serves as a readings recorder for the electrical, continuous remote indication of the filling level.
The operation of the measuring devices is based on the float principle. Through the wall of a guide tube the magnetic field, which is contained in the
spherical or cylindrical float, triggers reed contacts, which uninterruptedly pick up the measuring voltage given at a resistance measuring chain.
The measuring voltage is proportional to the height of the filling level ( 3-wire potentiometer circuit ). The size of the reed contacts is made up in different accuracy’s.
In connection with a control unit the resistance value can be converted into a standardised analogue value, e.g. 4 …20 mA.